How to Select a Surge Arrester for a 3.75 MVA, 13.2 kV Transformer: Voltage Ratings, MCOV, and Grounding Requirements (11/25/2026)


Selecting a surge arrester for a 3.75 MVA, 13.2 kV transformer requires evaluating system grounding, maximum continuous operating voltage (MCOV), temporary overvoltages, and transformer insulation levels. This engineering guide explains arrester sizing, IEEE standards, NEC requirements, and insulation coordination for medium-voltage transformer protection.

By LarsonElectronics.com and November 25, 2026

For a 3.75 MVA transformer operating on a nominal 13.2 kV system, a 10 kV surge arrester with an 8.4 kV maximum continuous operating voltage (MCOV) is a common preliminary selection for a four-wire, effectively grounded, multigrounded-neutral distribution system. Three-wire grounded systems may require a 15 kV arrester with a 12.7 kV MCOV or another suitable rating, while ungrounded systems commonly warrant evaluation of an 18 kV arrester with a 15.3 kV MCOV.

Final surge arrester selection depends on maximum system operating voltage, system grounding, temporary overvoltage magnitude and duration, transformer insulation withstand capability, and the protective characteristics of the selected arrester.

The 3.75 MVA transformer capacity does not directly determine the required surge arrester voltage rating. Instead, engineers must evaluate the electrical characteristics of the system supplying the transformer.

Proper surge arrester selection is essential for protecting industrial power and distribution transformers against lightning-induced surges, switching transients, and other transient overvoltages that could damage winding insulation, bushings, cable terminations, and associated electrical equipment.

What Size Surge Arrester Is Required for a 3.75 MVA, 13.2 kV Transformer

The required surge arrester voltage rating depends primarily on the grounding configuration and maximum phase-to-ground voltage at the arrester installation location.

Preliminary surge arrester selections for nominal 13.2 kV electrical systems
System Grounding Configuration Candidate Duty-Cycle Voltage Rating Typical MCOV Engineering Consideration
Four-wire effectively grounded wye with multigrounded neutral 10 kV 8.4 kV Common preliminary selection for grounded distribution systems
Three-wire system with solidly grounded source neutral 15 kV candidate 12.7 kV Verify ground-fault voltage rise, grounding effectiveness, and clearing time
Ungrounded delta or ungrounded wye 18 kV candidate 15.3 kV Unfaulted phases may experience approximately full line-to-line voltage relative to ground
Resistance-grounded or impedance-grounded system Application-specific Application-specific Requires evaluation of neutral displacement and temporary overvoltage duration

These ratings are preliminary engineering examples for phase-to-ground connected metal-oxide surge arresters. They are not universal equipment specifications. Manufacturer-specific application tables, temporary overvoltage curves, and protective characteristics must be evaluated before purchasing or installing an arrester.

Some three-wire grounded systems may permit lower arrester ratings than those shown, provided the actual grounding characteristics, temporary overvoltages, and manufacturer withstand capabilities support the selection.

Why Transformer MVA Does Not Directly Determine Surge Arrester Voltage Rating

A transformer's MVA rating establishes its apparent power capacity under specified operating conditions. Surge arrester voltage ratings, however, are established primarily by the voltage appearing across the arrester during normal and abnormal system conditions.

A 750 kVA transformer, a 2.5 MVA transformer, and a 3.75 MVA transformer connected to the same 13.2 kV distribution system may require arresters with identical voltage and MCOV ratings.

Nevertheless, transformer size and application can influence other arrester selection considerations, including:

  • Required surge energy handling capability.
  • Transformer insulation withstand characteristics.
  • Equipment replacement cost and operational criticality.
  • Available short-circuit current at the installation location.
  • Transformer switching characteristics.
  • Required arrester performance classification.
  • Exposure to lightning and repetitive switching events.
  • Substation insulation coordination requirements.

Engineers should distinguish between selecting the correct arrester voltage rating and selecting the appropriate arrester construction, performance class, and energy-handling capability.

How to Calculate the Primary Current of a 3.75 MVA Transformer

Although transformer current does not directly establish arrester MCOV, calculating the transformer full-load current provides useful information for the overall electrical system design.

For a balanced three-phase transformer, rated primary current is calculated as:

Primary current (A) = Transformer apparent power (kVA) × 1,000 ÷ (v3 × Primary line-to-line voltage)

For a 3.75 MVA transformer operating at 13,200 volts:

Primary current = 3,750 × 1,000 ÷ (1.732 × 13,200)

Primary current = approximately 164 A

The transformer has a rated primary current of approximately 164 amperes at nominal voltage.

This calculation is relevant to primary conductors, switching equipment, protective devices, and transformer circuit design. It does not mean that the surge arrester requires a continuous current rating of 164 amperes.

Unlike equipment connected in series with the transformer, a conventional phase-to-ground surge arrester is connected in parallel with the protected circuit. Under normal operating conditions, a metal-oxide arrester conducts only a small leakage current.

How Metal-Oxide Surge Arresters Protect Transformers

Modern medium-voltage surge arresters commonly contain nonlinear metal-oxide varistors (MOVs), typically based on zinc oxide materials.

Under normal system voltage, the arrester presents high electrical impedance and conducts relatively little current. During a transient overvoltage, its impedance decreases significantly, allowing surge current to flow toward the grounding system while limiting the voltage imposed on the protected equipment.

After the transient dissipates, the arrester returns to its normal high-impedance operating condition, provided its electrical and thermal capabilities have not been exceeded.

Surge arresters do not completely eliminate transient voltages. Instead, they limit the voltage appearing across their terminals to a level determined by their nonlinear protective characteristics, surge current magnitude, and waveform.

Surge arresters are not substitutes for fuses, circuit breakers, differential protection, or other equipment intended to interrupt sustained electrical faults.

How to Calculate Phase-to-Ground Voltage on a 13.2 kV System

For a balanced three-phase system with a stable grounded neutral reference, nominal phase-to-ground voltage is calculated by dividing the line-to-line voltage by the square root of three.

Phase-to-ground voltage = Line-to-line voltage ÷ v3

For a nominal 13.2 kV system:

Phase-to-ground voltage = 13.2 ÷ 1.732 = approximately 7.62 kV

The nominal phase-to-ground operating voltage is approximately 7,620 volts.

However, arrester selection must be based on the maximum continuous operating voltage at the installation location rather than nominal voltage alone.

Calculating Maximum Continuous Phase-to-Ground Voltage

Assume the nominal 13.2 kV distribution system has a maximum operating line-to-line voltage of 13.97 kV, consistent with a commonly referenced North American distribution voltage range.

The corresponding balanced phase-to-ground voltage is:

Maximum phase-to-ground voltage = 13.97 ÷ 1.732

Maximum phase-to-ground voltage = approximately 8.07 kV

An arrester with an 8.4 kV MCOV exceeds this calculated maximum continuous phase-to-ground voltage.

By comparison, an arrester with a 7.65 kV MCOV would be below the assumed maximum continuous voltage and would not satisfy this operating condition.

The actual maximum system voltage must be obtained from the utility or established through the facility electrical design. The illustrative value of 13.97 kV should not automatically be applied to every 13.2 kV installation.

What Maximum Continuous Operating Voltage Means

Maximum continuous operating voltage, abbreviated MCOV, is the designated RMS power-frequency voltage that may be continuously applied across the terminals of an arrester under its specified service conditions.

MCOV is one of the most important electrical parameters used when selecting a metal-oxide surge arrester.

If the continuously applied voltage exceeds the arrester's MCOV, increased electrical conduction and heating may occur. Prolonged operation outside the arrester's intended voltage capability can contribute to thermal instability, accelerated deterioration, or equipment failure.

Engineers should select an MCOV that accommodates the maximum continuous voltage expected across the arrester while separately verifying temporary overvoltage withstand capability.

MCOV should not be confused with:

  • Nominal electrical system voltage.
  • Maximum system line-to-line operating voltage.
  • Arrester duty-cycle voltage rating.
  • Transformer basic lightning impulse insulation level.
  • Arrester discharge or residual voltage.
  • Temporary overvoltage withstand capability.

How MCOV Differs From the Arrester Duty-Cycle Voltage Rating

The IEEE arrester duty-cycle voltage rating identifies a voltage associated with standardized operating-duty performance requirements. MCOV identifies the power-frequency voltage that may be continuously applied across the arrester.

These values are related but are not interchangeable.

Common North American metal-oxide surge arrester voltage rating combinations
Duty-Cycle Voltage Rating Typical MCOV
6 kV 5.1 kV
9 kV 7.65 kV
10 kV 8.4 kV
12 kV 10.2 kV
15 kV 12.7 kV
18 kV 15.3 kV
21 kV 17.0 kV
24 kV 19.5 kV
27 kV 22.0 kV
30 kV 24.4 kV
36 kV 29.0 kV

These combinations are representative of commonly available products. Buyers must verify the exact duty-cycle rating, MCOV, temporary overvoltage capabilities, and protective characteristics of the selected manufacturer's arrester.

A 10 kV arrester with an 8.4 kV MCOV can be appropriate for a nominal 13.2 kV electrical system because the arrester is connected between an individual phase and ground rather than continuously subjected to the entire line-to-line voltage.

How Electrical System Grounding Affects Surge Arrester Selection

Electrical system grounding determines how phase-to-ground voltages behave during normal operation and ground-fault conditions.

Two transformers with identical voltage and MVA ratings may require different surge arresters when installed on systems with different grounding arrangements.

Four-Wire Effectively Grounded Wye Systems

On a four-wire, effectively grounded distribution system with a multigrounded neutral, phase-to-ground voltage is normally maintained relatively close to the nominal line-to-neutral voltage.

For a nominal 13.2 kV system, the normal balanced phase-to-ground voltage is approximately 7.62 kV.

Assuming a maximum line-to-line operating voltage of 13.97 kV, an arrester with an 8.4 kV MCOV is a common preliminary selection.

A typical corresponding duty-cycle voltage rating is 10 kV.

The final selection must still account for ground-fault overvoltages, system configuration changes, fault-clearing time, and manufacturer-specific temporary overvoltage capabilities.

Three-Wire Systems With Solidly Grounded Source Neutrals

A three-wire distribution system may have a solidly grounded source transformer neutral without distributing a neutral conductor throughout the circuit.

Depending on source impedance, grounding paths, and fault location, the voltage rise on unfaulted phases during a ground fault may differ from that experienced on a multigrounded-neutral distribution system.

Certain manufacturer application tables identify a 15 kV arrester with a 12.7 kV MCOV as a preliminary candidate for this type of nominal 13.2 kV system. Other manufacturer guidance may permit different ratings depending on actual grounding effectiveness and arrester temporary overvoltage performance.

The presence of a solidly grounded neutral at the source does not independently establish the phase-to-ground voltage conditions at every point on the system.

Ungrounded Delta and Ungrounded Wye Systems

During normal balanced operation, phase-to-ground voltages on an ungrounded system may be approximately equal to the line-to-line voltage divided by the square root of three because of distributed system capacitance.

However, during a single-phase ground fault, the system neutral reference can shift. The voltage of each unfaulted phase relative to ground may approach the full line-to-line system voltage.

For a nominal 13.2 kV ungrounded system, an unfaulted phase may therefore experience approximately 13.2 kV relative to ground during a ground fault under idealized conditions.

If the system is operating at 13.97 kV when the ground fault occurs, the corresponding unfaulted phase-to-ground voltage may approach 13.97 kV.

An 18 kV arrester with a 15.3 kV MCOV is a common candidate when evaluating arresters for systems that may experience prolonged neutral displacement.

A 15 kV arrester with a 12.7 kV MCOV is below the possible sustained phase-to-ground voltage in this example. It should not be assumed suitable without a documented temporary overvoltage assessment and manufacturer approval.

Intermittent arcing ground faults and resonant conditions may produce additional overvoltages beyond the simplified neutral displacement calculation.

Resistance-Grounded and Impedance-Grounded Systems

Resistance-grounded and impedance-grounded systems limit ground-fault current through an intentional grounding impedance.

These systems are frequently used in industrial process facilities, mining operations, manufacturing plants, and other installations where ground-fault behavior and service continuity are important design considerations.

Arrester selection depends on:

  • Neutral grounding resistance or impedance.
  • System zero-sequence impedance.
  • Ground-fault current magnitude.
  • Neutral displacement during ground faults.
  • Maximum duration of ground-fault operation.
  • Ground-fault detection and clearing arrangements.
  • System capacitance and possible resonant conditions.

High-resistance-grounded systems that permit continued operation during a first ground fault may require arresters capable of withstanding prolonged elevated phase-to-ground voltages.

A grounding resistor limits fault current but does not necessarily prevent substantial voltage rise on unfaulted phases.

Why Transformer Winding Configuration Does Not Independently Determine Arrester Rating

Transformer winding configuration and electrical system grounding are related but distinct engineering considerations.

A transformer with a delta-connected primary winding can be supplied by an effectively grounded utility distribution system. In this case, primary-side arrester selection should reflect the grounding characteristics of the supplying system rather than automatically treating the circuit as ungrounded.

Similarly, a wye-connected transformer winding does not establish an effectively grounded electrical system unless the neutral connections and overall system impedance provide the required grounding characteristics.

Relationship between transformer winding configuration and supply system grounding
Transformer Primary Configuration Supply System Arrester Selection Basis
Delta Effectively grounded utility distribution Actual supply system phase-to-ground voltage and TOV characteristics
Delta Ungrounded industrial distribution Neutral displacement and ground-fault duration
Grounded wye Grounded electrical system Verified system grounding effectiveness and maximum operating voltage
Ungrounded wye Ungrounded electrical system Elevated phase-to-ground voltage during ground faults

Engineers should review the complete system one-line diagram, transformer winding connections, neutral grounding arrangements, and applicable fault studies before specifying surge arresters.

How Effective Grounding Is Evaluated

Effective grounding is an electrical system characteristic that limits phase-to-ground voltage rise during ground faults.

A commonly used engineering screening criterion for effectively grounded systems is a positive zero-sequence-to-positive-sequence reactance ratio not exceeding three, together with a nonnegative zero-sequence resistance-to-positive-sequence reactance ratio not exceeding one.

These relationships are commonly expressed as:

  • 0 < X0/X1 = 3
  • 0 = R0/X1 = 1

Where X0 represents zero-sequence reactance, X1 represents positive-sequence reactance, and R0 represents zero-sequence resistance.

These simplified criteria should be applied within the appropriate engineering framework. Complex networks may require direct calculation of phase-to-ground voltages during credible ground-fault and operating conditions.

Grounding effectiveness should be evaluated at the relevant arrester installation location and under applicable system configurations rather than inferred solely from transformer neutral connections.

Why Temporary Overvoltage Is Critical to Arrester Selection

A temporary overvoltage (TOV) is a relatively sustained power-frequency overvoltage that can persist for multiple electrical cycles, seconds, or longer, depending on the initiating event and system protection response.

Unlike short-duration lightning impulses, temporary overvoltages can subject metal-oxide arresters to sustained electrical conduction and thermal stress.

Common sources of temporary overvoltage include:

  • Single-phase ground faults.
  • Neutral displacement on ungrounded or impedance-grounded systems.
  • Sudden load rejection.
  • Ferroresonance.
  • Abnormal transformer energization conditions.
  • Loss of a grounding source.
  • Network resonance.
  • Abnormal voltage regulator operation.
  • Islanding and distributed generation operating conditions.

Arrester manufacturers publish temporary overvoltage withstand curves that identify permissible voltage exposure as a function of time under defined conditions.

These curves may account for prior surge energy exposure, ambient temperature, and other operating assumptions.

An arrester may safely withstand a voltage exceeding its MCOV for a limited duration. The allowable duration must be established from the selected product's technical documentation rather than a universal multiplier.

Temporary Overvoltage Calculation Example

Consider a 13.2 kV industrial electrical system experiencing an unfaulted phase-to-ground voltage of 13.2 kV during a ground fault.

Comparison of illustrative temporary overvoltage exposure relative to arrester MCOV
Arrester Duty-Cycle Rating MCOV Applied Voltage Divided by MCOV
10 kV 8.4 kV 1.57 per unit
12 kV 10.2 kV 1.29 per unit
15 kV 12.7 kV 1.04 per unit
18 kV 15.3 kV 0.86 per unit

These calculations demonstrate the relative voltage exposure of different arrester ratings during the assumed ground fault. They do not establish permissible exposure durations or confirm equipment suitability.

For each candidate arrester, the calculated overvoltage magnitude and expected duration must be compared with the manufacturer's applicable TOV withstand curve.

Why Selecting the Highest Available Arrester Voltage Rating Is Not Always Appropriate

Selecting an unnecessarily high arrester voltage rating may reduce the effectiveness of transformer insulation protection.

For otherwise comparable arrester designs, higher MCOV and duty-cycle voltage ratings generally correspond to higher discharge voltage characteristics at a given surge current.

A higher-rated arrester may therefore withstand greater temporary overvoltage exposure while allowing a higher transient voltage to appear at the transformer terminals.

Conversely, an arrester with an excessively low voltage rating may provide favorable transient voltage limitation but be unable to withstand normal operating voltage or temporary overvoltage conditions.

The engineering objective is to select an arrester that:

  • Withstands maximum continuous operating voltage.
  • Survives credible temporary overvoltage conditions.
  • Provides adequate insulation protective margins.
  • Accommodates expected surge energy and charge transfer.
  • Meets applicable electrical, mechanical, and environmental requirements.

Arrester selection represents a balance between equipment protection and arrester survivability.

How Transformer BIL Affects Surge Arrester Selection

Basic lightning impulse insulation level (BIL) identifies a standardized lightning impulse voltage withstand level associated with transformer insulation.

Transformer BIL is expressed in kilovolts crest and is distinct from continuous operating voltage, which is generally expressed in RMS kilovolts.

Many North American transformers in the 15 kV equipment class have a specified primary BIL of 95 kV. However, other insulation levels may apply depending on transformer construction, equipment specifications, applicable standards, and intended service.

A 3.75 MVA transformer operating at 13.2 kV should not automatically be assumed to have a 95 kV BIL. Buyers must verify the actual transformer nameplate information, certified drawings, or manufacturer technical documentation.

Surge arresters should be coordinated with the withstand characteristics of transformer windings, bushings, cable terminations, and other protected insulation systems.

How to Calculate Transformer Surge Protection Margin

A simplified lightning impulse protective margin can be calculated by comparing equipment BIL with the expected protective voltage at the equipment terminals.

Protective margin (%) = [(Equipment BIL ÷ Protective voltage) - 1] × 100

For an illustrative transformer with a verified BIL of 95 kV and an assumed effective protective voltage of 45 kV crest at its terminals:

Protective margin = [(95 ÷ 45) - 1] × 100

Protective margin = approximately 111 percent

This simplified calculation indicates the ratio between the assumed protective voltage and specified insulation withstand level. It does not independently establish acceptable insulation coordination.

A complete engineering assessment should consider:

  • Arrester discharge voltage at relevant surge currents.
  • Front-of-wave protective characteristics.
  • Switching impulse protective characteristics where applicable.
  • Voltage developed across arrester connecting leads.
  • Separation distance between the arrester and transformer.
  • Traveling wave reflections.
  • Transformer and connected equipment insulation withstand levels.
  • Applicable engineering protective margin criteria.

The example uses hypothetical protective voltage data and does not represent the guaranteed performance of a specific arrester.

IEEE C62.22 and IEEE 1313 series insulation coordination guidance provide relevant engineering frameworks for establishing appropriate protective margins.

How Arrester Discharge Voltage Differs From MCOV

Arrester discharge voltage, sometimes referred to as residual voltage, is the voltage appearing across the arrester while it conducts a specified surge current.

Unlike MCOV, which describes continuous power-frequency voltage capability, discharge voltage describes transient protective performance.

Manufacturers typically provide discharge voltage characteristics at specified current magnitudes and waveforms.

Relevant protective characteristics may include:

  • Lightning impulse discharge voltage.
  • Steep-current impulse or front-of-wave protective voltage.
  • Switching impulse discharge voltage.
  • Discharge voltage at multiple surge current magnitudes.

A 10 kV arrester does not limit transient voltage to 10 kV. Its actual discharge voltage during a surge may be substantially higher than its duty-cycle voltage rating or MCOV.

Transformer insulation coordination must therefore use the arrester's published protective characteristics rather than its nominal voltage designation alone.

How Distribution, Intermediate, and Station-Class Arresters Differ

Metal-oxide surge arresters are available in several performance categories intended for different electrical system applications and operating duties.

General comparison of IEEE surge arrester application classes
Arrester Class Typical Applications Engineering Considerations
Distribution Class Distribution lines, distribution transformers, and industrial distribution equipment Expected surge exposure, applicable endurance classification, and protective characteristics
Intermediate Class Selected industrial substations and power distribution equipment Protective performance, surge duty, and equipment criticality
Station Class Substations, power transformers, and critical electrical infrastructure Energy handling, charge transfer, insulation coordination, and higher-consequence applications

A 3.75 MVA industrial transformer may be protected by distribution, intermediate, or station-class arresters depending on the specific installation and engineering requirements.

There is no universal transformer MVA threshold above which station-class surge arresters automatically become mandatory.

For high-value transformers serving critical manufacturing operations, data centers, utilities, or industrial process loads, engineers may evaluate station-class arresters because of their available protective characteristics and surge-duty capabilities.

Final class selection should be based on verified equipment performance rather than classification terminology alone.

How Surge Current and Energy Handling Affect Arrester Selection

Arrester voltage rating establishes only part of the equipment's required electrical performance.

The selected arrester must also withstand the expected surge current, transferred charge, absorbed energy, and repetitive electrical duty associated with its installation.

A commonly encountered nominal discharge current designation for medium-voltage arresters is 10 kA. However, this designation alone does not establish total energy-handling capability, maximum survivable current, or short-circuit performance.

Relevant selection parameters may include:

  • Nominal discharge current.
  • High-current impulse withstand capability.
  • Repetitive charge transfer capability.
  • Thermal energy handling capability.
  • Operating-duty performance.
  • Temporary overvoltage withstand characteristics.
  • Short-circuit performance rating.

The electrical system's available power-frequency fault current should be evaluated separately from the arrester's surge discharge current rating.

For example, a 10 kA nominal discharge current designation does not mean that the arrester provides a 10 kA circuit breaker interrupting capability.

Why Arrester Short-Circuit Performance Matters

A surge arrester that experiences electrical or thermal failure may develop an internal fault and conduct power-frequency fault current supplied by the connected electrical system.

The arrester's applicable short-circuit performance rating should therefore be evaluated against the prospective fault current at its installation location under the manufacturer's specified test conditions.

Short-circuit qualification addresses equipment behavior during defined failure and fault conditions. It does not mean that the surge arrester can independently interrupt the available electrical system fault current.

Upstream fuses, circuit breakers, and protective relays must provide appropriate fault isolation.

Where an arrester incorporates a ground lead disconnector or other failure indication device, its operation and limitations should be reviewed as part of the overall protection design.

How Surge Arrester Location Affects Transformer Protection

Surge arresters should generally be installed electrically close to the transformer terminals they are intended to protect, subject to equipment manufacturer instructions, required electrical clearances, and installation constraints.

The voltage experienced at the transformer terminals during a surge can exceed the arrester's published discharge voltage because of connecting lead inductance, separation distance, and traveling wave effects.

Important installation considerations include:

  • Minimizing unnecessary phase connection lead length.
  • Minimizing unnecessary grounding lead length.
  • Avoiding unnecessarily large conductor loops.
  • Providing an appropriate low-impedance grounding and bonding arrangement.
  • Maintaining required phase-to-phase and phase-to-ground clearances.
  • Following manufacturer mounting and terminal requirements.
  • Evaluating electrical separation between the arrester and the protected equipment.

The arrester grounding connection and transformer enclosure bonding should be coordinated to minimize potential differences during surge discharge.

Arresters installed at a remote incoming switchgear location may not provide adequate protection at transformer terminals under all surge conditions.

Illustrative Arrester Lead Inductance Calculation

The transient voltage developed across a conductor inductance can be approximated using the following relationship:

Inductive voltage = Inductance × Rate of current change

Assume a simplified effective connection inductance of 1 microhenry and a surge current rise rate of 10 kA per microsecond.

Inductive voltage = approximately 10 kV

Under this hypothetical condition, connection inductance could contribute an additional transient voltage of approximately 10 kV.

The actual voltage contribution depends on conductor geometry, current waveform, grounding arrangement, electromagnetic coupling, and installation configuration.

This example illustrates why surge arrester installation geometry can materially affect transformer protection even when the arrester itself has been correctly rated.

How Surge Arresters Are Applied to Pad-Mounted and Substation Transformers

Surge arrester construction and installation arrangements depend on the transformer design and associated distribution system.

Pad-Mounted Transformers

Pad-mounted transformers may use dead-front elbow arresters, parking stand arrangements, or other manufacturer-approved arrester assemblies compatible with the primary termination system.

Selection should consider:

  • Bushing interface compatibility.
  • Loadbreak or deadbreak connector construction.
  • Voltage class and MCOV.
  • Primary cable configuration.
  • Available accessory mounting space.
  • Loop-feed or radial-feed arrangements.
  • Applicable equipment operating and safety procedures.

IEEE 386 provides relevant requirements for applicable separable insulated connector systems. Connector interface compatibility must be verified independently of arrester voltage selection.

Substation and Outdoor Power Transformers

Substation transformers frequently use separately mounted outdoor surge arresters connected near the high-voltage bushings or incoming equipment terminals.

Engineering considerations may include:

  • Arrester mounting structure.
  • Electrical clearances.
  • Terminal mechanical loading.
  • Environmental and contamination exposure.
  • Grounding conductor arrangements.
  • Insulation coordination with adjacent switchgear.
  • Accessibility for inspection and maintenance.

Transformer suppliers should coordinate arrester mounting provisions and connection arrangements with the purchaser's electrical system design.

Whether Transformers Require Surge Arresters on Both Primary and Secondary Sides

Primary-side surge arresters do not automatically provide adequate protection for every secondary-side overvoltage condition.

Transient voltages may be transferred through transformer windings by electromagnetic and capacitive coupling. Additional surges may originate within the secondary electrical system.

Secondary-side surge protection requirements depend on:

  • Transformer winding configuration.
  • Primary and secondary voltage ratings.
  • Electrical system grounding.
  • Connected equipment insulation withstand levels.
  • Secondary conductor length and exposure.
  • Switching equipment and motor loads.
  • Presence of variable frequency drives or sensitive electronic equipment.
  • Applicable installation codes.

For a transformer with a 13.2 kV primary and a 480 V secondary, the primary system generally requires medium-voltage surge arresters, while the secondary system may require appropriately rated low-voltage surge protective devices.

Low-voltage surge protective devices are subject to different product standards, installation requirements, and voltage rating terminology.

Primary and secondary surge protection should be evaluated as coordinated elements of the complete electrical distribution system.

How Surge Arrester Selection Changes With Common Transformer Voltages

North American industrial distribution systems commonly operate at nominal voltages including 4.16 kV, 12.47 kV, 13.2 kV, 13.8 kV, 24.94 kV, 27.6 kV, and 34.5 kV.

The following examples illustrate how nominal system voltage and grounding influence preliminary MCOV selection.

Illustrative surge arrester MCOV candidates for common medium-voltage systems
Nominal Line-to-Line Voltage Assumed Maximum Line-to-Line Voltage Effectively Grounded System MCOV Candidate Ungrounded or Impedance-Grounded System MCOV Candidate
4.16 kV 4.40 kV 2.55 kV 5.1 kV
12.47 kV 13.20 kV 7.65 kV 15.3 kV
13.2 kV 13.97 kV 8.4 kV 15.3 kV
13.8 kV 14.52 kV 8.4 kV 15.3 kV
24.94 kV 26.40 kV 15.3 kV 29.0 kV
27.6 kV 29.30 kV 18.0 kV or application-specific higher rating Application-specific
34.5 kV 36.50 kV 22.0 kV Application-specific

These values are preliminary application examples based on representative system voltages and manufacturer guidance. They must not be used as a universal purchasing table without verification of temporary overvoltages, grounding conditions, voltage regulation, and insulation coordination.

Where the maximum phase-to-ground voltage approaches the stated MCOV, the actual utility voltage range and operating tolerances require particular attention.

Which IEEE Standards Apply to Transformer Surge Arrester Selection

Transformer surge protection should be engineered using applicable equipment standards, arrester application guides, insulation coordination principles, and manufacturer technical documentation.

Relevant standards for transformer surge protection and arrester application
Standard Engineering Application
IEEE C62.11 Metal-oxide surge arrester performance requirements and testing for applicable AC power circuits above 1 kV
IEEE C62.22 Application guidance for metal-oxide surge arresters on AC systems above 1,000 volts
IEEE C62.22.1 Connection and application guidance for surge arresters protecting shielded electric power cable systems within the standard's scope
IEEE 1313 Series Insulation coordination definitions, principles, and application guidance
IEEE C57.12.00 General requirements for applicable liquid-immersed distribution, power, and regulating transformers
IEEE C57.12.01 General requirements for applicable dry-type distribution and power transformers
IEEE C57.12.90 Test procedures for applicable liquid-immersed transformers
IEEE 386 Requirements for applicable separable insulated connector systems
IEEE 80 AC substation grounding safety guidance
ANSI C84.1 Nominal voltage ratings and operating voltage tolerances for applicable 60 Hz electrical power systems
IEC 60099-4 Requirements for applicable gapless metal-oxide surge arresters for AC systems
IEC 60071 Series Insulation coordination principles and application guidance

IEEE C62.11 establishes arrester equipment requirements and standardized qualification procedures. IEEE C62.22 provides application guidance for selecting and applying metal-oxide arresters.

Compliance with an arrester product standard does not independently establish suitability for a particular transformer installation. The selected arrester must also satisfy the project's electrical system conditions and insulation coordination requirements.

Engineers should identify the applicable published standard editions, amendments, and contractual requirements. Proposed revisions and active standards development projects should not be treated as published mandatory requirements.

How NEC Requirements Apply to Transformer Surge Arresters

In the United States, surge arrester installations within the scope of NFPA 70, the National Electrical Code (NEC), must comply with the edition adopted by the applicable authority having jurisdiction.

Recent NEC editions address overvoltage protection under Article 242, including surge arrester requirements for applicable medium-voltage and higher-voltage installations.

Older adopted NEC editions may retain surge arrester requirements under Article 280 and low-voltage surge protective device requirements under Article 285.

NEC provisions relevant to transformer surge protection
NEC Reference General Application
Article 242 Applicable overvoltage protection and surge arrester requirements in newer NEC editions
Article 250 Grounding and bonding of electrical systems and equipment
Article 450 Transformer installation and protection requirements within the article's scope
Section 110.3 Equipment suitability, examination, and applicable installation instructions
Sections 110.9 and 110.10 Applicable interrupting ratings and equipment coordination with electrical fault characteristics
Article 490 Applicable higher-voltage equipment requirements according to the adopted NEC edition

The NEC establishes electrical installation safety requirements. It does not replace a transformer insulation coordination study or detailed manufacturer arrester application analysis.

Certain utility-controlled installations may fall outside the NEC's scope when the applicable exclusion conditions are satisfied. Such installations may instead be governed by IEEE C2, the National Electrical Safety Code (NESC), utility engineering standards, and other regulatory requirements.

How Canadian Electrical Requirements Affect Surge Arrester Selection

Canadian industrial and utility installations may use distribution system voltages and grounding arrangements similar to those encountered in the United States, including 13.2 kV, 13.8 kV, 27.6 kV, and 34.5 kV systems.

Applicable Canadian requirements may include:

  • CSA C22.1, Canadian Electrical Code, Part I.
  • Section 36 requirements for applicable high-voltage installations.
  • Section 10 grounding and bonding requirements.
  • Provincial and territorial electrical safety regulations.
  • Electrical equipment approval requirements.
  • Utility-specific distribution and interconnection standards.
  • Applicable IEEE, IEC, and CSA equipment standards.

Although the fundamental electrical principles governing arrester selection are consistent across North America, utility voltage tolerances, equipment approval requirements, installation preferences, and grounding practices may differ.

For Canadian projects, buyers should verify applicable requirements with the local utility, electrical engineering team, equipment manufacturer, and authority having jurisdiction.

Industrial Example of a 3.75 MVA Manufacturing Facility Transformer

Consider a manufacturing facility installing a 3.75 MVA, 13.2 kV to 480Y/277 V transformer supplied by an effectively grounded utility distribution system.

Assume the following electrical characteristics:

  • Nominal primary voltage of 13.2 kV.
  • Maximum primary operating voltage of 13.97 kV.
  • Four-wire multigrounded-neutral utility distribution.
  • Verified transformer primary BIL of 95 kV.
  • Primary-side phase-to-ground surge arresters.

The calculated maximum continuous phase-to-ground voltage is approximately 8.07 kV.

A 10 kV arrester with an 8.4 kV MCOV would be a reasonable preliminary candidate.

Before final selection, the engineering team should verify temporary overvoltage withstand capability, arrester protective voltage characteristics, anticipated surge exposure, available fault current, grounding arrangements, and separation distance between the arresters and transformer terminals.

If the same transformer were installed on an ungrounded industrial distribution system instead, the preliminary candidate could change to an 18 kV arrester with a 15.3 kV MCOV because unfaulted phase-to-ground voltages could approach the full line-to-line voltage during a ground fault.

This example demonstrates why transformer MVA and nominal primary voltage alone cannot establish a complete surge arrester specification.

Industrial Example of a Resistance-Grounded Mining Facility

Consider a mining operation using a 13.2 kV resistance-grounded distribution system supplying multiple industrial transformers and large motor loads.

The facility's grounding philosophy may permit continued operation during an initial ground fault, depending on its protection design and applicable safety requirements.

Because the unfaulted phases may experience elevated phase-to-ground voltages for an extended period, surge arresters selected using normal balanced phase-to-ground voltage alone could be subjected to excessive temporary overvoltage stress.

The engineering team should establish the maximum credible voltage exposure, duration of ground-fault operation, and required arrester MCOV before evaluating protective margins and surge-duty capabilities.

In this application, fault duration and grounding characteristics may be more important to arrester voltage selection than the individual transformer's apparent power rating.

Common Mistakes When Selecting Transformer Surge Arresters

Common surge arrester specification errors and their engineering consequences
Selection Mistake Potential Consequence Recommended Engineering Approach
Selecting the arrester solely from transformer MVA Incorrect voltage rating Evaluate actual system voltage and grounding
Using nominal voltage instead of maximum operating voltage Continuous voltage exposure above MCOV Obtain verified utility or facility maximum voltage data
Assuming every delta-connected transformer is supplied by an ungrounded system Unnecessarily high or otherwise unsuitable arrester rating Evaluate actual source grounding characteristics
Assuming a 15 kV arrester is always appropriate for a 13.2 kV ungrounded system Possible excessive TOV exposure Evaluate neutral displacement, fault duration, and manufacturer TOV curves
Selecting the highest available arrester rating Reduced transformer insulation protective margin Balance arrester voltage withstand and protective characteristics
Confusing nominal discharge current with fault current capability Incorrect equipment duty assessment Review surge-duty and short-circuit characteristics separately
Ignoring transformer BIL Insufficient insulation coordination Compare actual arrester protective levels with equipment withstand characteristics
Installing arresters with unnecessarily long connection leads Increased transient voltage at equipment terminals Optimize installation geometry and grounding arrangements

Transformer Surge Arrester Procurement Checklist

Industrial buyers and electrical engineers should establish the following information before specifying or purchasing surge arresters for medium-voltage transformers.

Engineering procurement checklist for transformer surge arresters
Specification Category Required Information
Transformer Capacity Rated kVA or MVA and intended application
Nominal System Voltage Primary and secondary line-to-line voltage ratings
Maximum Operating Voltage Verified maximum continuous voltage at the installation location
System Grounding Source grounding configuration, neutral arrangements, and grounding effectiveness
Transformer Winding Configuration Primary and secondary connections and associated grounding arrangements
Temporary Overvoltage Expected voltage magnitude, duration, and manufacturer withstand curves
Arrester Duty-Cycle Rating Specified IEEE voltage rating
MCOV Maximum continuous operating voltage capability
Transformer Insulation Level Verified BIL and other applicable insulation withstand characteristics
Protective Characteristics Discharge voltage and applicable impulse protective levels
Surge Duty Expected discharge current, energy, charge transfer, and repetitive surge exposure
Short-Circuit Performance Applicable arrester qualification compared with prospective fault current
Arrester Class Distribution, intermediate, station, or other applicable equipment classification
Installation Configuration Mounting arrangements, connector compatibility, lead lengths, and grounding
Environmental Requirements Temperature, altitude, pollution, moisture, corrosion, and indoor or outdoor exposure
Applicable Standards IEEE, NEC, CSA, IEC, utility, and jurisdictional requirements

Final equipment approval should be based on a documented engineering assessment supported by manufacturer technical data and applicable electrical system studies.

Frequently Asked Questions About Transformer Surge Arrester Selection

The recommended surge arrester size for a 3.75 MVA, 13.2 kV transformer

A 10 kV surge arrester with an 8.4 kV MCOV is a common preliminary selection for a 13.2 kV effectively grounded, multigrounded-neutral distribution system. Ungrounded systems commonly warrant evaluation of an 18 kV arrester with a 15.3 kV MCOV. Final selection requires verification of grounding, maximum operating voltage, temporary overvoltages, and insulation coordination.

Whether transformer MVA determines surge arrester voltage rating

Transformer MVA does not directly determine surge arrester voltage rating. Arrester voltage selection depends primarily on maximum continuous phase-to-ground voltage, electrical system grounding, and temporary overvoltage conditions. Transformer capacity and application may influence other arrester performance and procurement considerations.

What MCOV is commonly used for a grounded 13.2 kV system

An 8.4 kV MCOV is commonly considered for an effectively grounded, multigrounded-neutral 13.2 kV distribution system. Three-wire grounded systems and other grounding configurations may require different MCOV values depending on temporary overvoltage conditions and grounding effectiveness.

Whether a 15 kV surge arrester is suitable for an ungrounded 13.2 kV system

A typical 15 kV arrester has a 12.7 kV MCOV, which is below the possible sustained phase-to-ground voltage on an unfaulted phase during a ground fault on a 13.2 kV ungrounded system. An 18 kV arrester with a 15.3 kV MCOV is a common candidate for evaluation. Lower ratings require documented temporary overvoltage verification.

Why a 10 kV surge arrester can protect a 13.2 kV transformer

A phase-to-ground surge arrester on an effectively grounded 13.2 kV system is normally exposed to phase-to-ground voltage rather than full line-to-line voltage. The nominal phase-to-ground voltage is approximately 7.62 kV, allowing an arrester with an 8.4 kV MCOV to be considered when maximum operating voltage and temporary overvoltage conditions permit.

Whether delta-connected transformer windings always require higher-rated surge arresters

Delta-connected transformer windings do not automatically require higher-rated surge arresters. The grounding characteristics of the electrical system supplying the transformer determine the relevant phase-to-ground voltages. A delta-connected transformer supplied by an effectively grounded utility system may use arresters appropriate for that grounded system.

Whether higher-rated surge arresters provide better transformer protection

Higher-rated surge arresters may withstand greater continuous or temporary voltage exposure, but they generally have higher discharge voltage characteristics within comparable product designs. Excessively high arrester ratings can reduce transformer insulation protective margins. Selection must balance arrester survivability and protective performance.

Whether a 3.75 MVA transformer requires station-class surge arresters

A 3.75 MVA transformer does not automatically require station-class surge arresters. The appropriate arrester class depends on insulation coordination, surge exposure, energy and charge transfer requirements, environmental conditions, available fault current, and equipment criticality.

Where surge arresters should be installed on a transformer

Surge arresters should generally be installed electrically close to the transformer terminals they protect, with appropriately arranged phase connections and grounding conductors. Installation must follow manufacturer requirements, electrical clearances, applicable codes, and insulation coordination recommendations.

Which IEEE standards govern medium-voltage transformer surge arrester selection

IEEE C62.11 establishes applicable metal-oxide surge arrester equipment requirements and testing procedures, while IEEE C62.22 provides arrester application guidance. IEEE transformer standards and applicable insulation coordination guidance provide additional requirements and engineering considerations.

Technical References and Engineering Resources

The following engineering resources provide additional guidance for medium-voltage surge arrester specification, transformer protection, electrical installation, and insulation coordination:

  • IEEE C62.11, Standard for Metal-Oxide Surge Arresters for AC Power Circuits Above 1 kV.
  • IEEE Standards Association, including IEEE C62.22 surge arrester application guidance and applicable transformer standards.
  • Eaton Overhead Line Installation and Protective Equipment Specifier's Guide, including representative arrester application ratings.
  • Hubbell Surge Arrester Technical Application Guide, including MCOV selection considerations for different grounding configurations.
  • United States Army Corps of Engineers Engineering Manual EM 1110-2-3006, including transformer surge arrester and insulation coordination guidance.
  • National Fire Protection Association, including NFPA 70, National Electrical Code, and applicable electrical safety standards.
  • CSA Group, including the Canadian Electrical Code and applicable electrical equipment requirements.
  • International Electrotechnical Commission, including IEC surge arrester and insulation coordination standards.

Engineering specifications should reference the applicable published standard editions and manufacturer technical documentation for the equipment under consideration.

Transformer Surge Protection and Industrial Electrical System Support

Selecting surge arresters for a 3.75 MVA, 13.2 kV transformer requires more than matching the transformer's voltage and apparent power ratings.

A 10 kV arrester with an 8.4 kV MCOV is a common preliminary candidate for an effectively grounded, multigrounded-neutral distribution system, while ungrounded systems may require evaluation of an 18 kV arrester with a 15.3 kV MCOV or another appropriately engineered rating.

Final selection must account for maximum operating voltage, grounding effectiveness, temporary overvoltage duration, transformer insulation withstand characteristics, discharge voltage, surge-duty capabilities, and installation geometry.

Larson Electronics provides industrial transformers for manufacturing facilities, commercial electrical systems, utilities, renewable energy infrastructure, mining operations, data centers, and other industrial power distribution applications.

Larson Electronics also offers after-sales support for low-voltage (LV), medium-voltage (MV), and high-voltage (HV) transformers and switchgear across North America, including assembly, installation, inspection, and commissioning services.

For assistance with transformer specifications, surge protection requirements, electrical system integration, or installation and commissioning support, contact Larson Electronics.