How to Select the Correct Surge Arrester Rating for a 2.5 MVA Transformer on a 13.2 kV System (11/19/2026)


Selecting a surge arrester for a 2.5 MVA transformer operating at 13.2 kV requires evaluating system grounding, maximum continuous operating voltage (MCOV), temporary overvoltages, transformer insulation levels, and IEEE surge protection standards. This engineering guide explains common arrester ratings, voltage calculations, insulation coordination, and selection considerations for grounded and ungrounded medium-voltage distribution systems.

By LarsonElectronics.com, November 19, 2026

Quick Answer: For a 2.5 MVA transformer supplied by a nominal 13.2 kV three-phase system, a 10 kV rated metal-oxide surge arrester with an 8.4 kV maximum continuous operating voltage (MCOV) is a common preliminary selection for a 13.2 kV grounded-wye, multigrounded-neutral distribution system. Other grounding configurations may require a higher arrester rating. A 15 kV arrester with a 12.7 kV MCOV may be appropriate for certain three-wire grounded systems, while ungrounded or delta systems may require an 18 kV arrester with a 15.3 kV MCOV or another rating supported by a temporary overvoltage study. Final selection must account for maximum operating voltage, grounding, fault-clearing time, transformer basic insulation level (BIL), and manufacturer performance data.

What Determines the Correct Surge Arrester Rating for a 2.5 MVA Transformer

The correct surge arrester rating is determined primarily by the electrical system voltage, grounding configuration, and expected overvoltage conditions rather than transformer capacity alone.

A 2.5 MVA transformer connected to a 13.2 kV distribution system may require different surge arresters depending on whether the source is a multigrounded-wye system, a three-wire grounded system, a resistance-grounded system, or an ungrounded delta system.

The selection process should evaluate:

  • Nominal and maximum system operating voltage
  • System grounding configuration and zero-sequence characteristics
  • Maximum continuous operating voltage (MCOV)
  • Temporary overvoltage (TOV) magnitude and duration
  • Transformer basic insulation level (BIL)
  • Arrester discharge voltage and protective margins
  • Lightning and switching surge exposure
  • Arrester energy handling and short-circuit capabilities
  • Installation location, conductor lengths, and grounding connections

These considerations are addressed through the application principles of IEEE C62.22 and the performance requirements of IEEE C62.11 for metal-oxide surge arresters.

How the 13.2 kV System Voltage Affects Surge Arrester Selection

A nominal 13.2 kV three-phase system normally identifies the line-to-line voltage. On a balanced grounded-wye system, the nominal phase-to-ground voltage is calculated by dividing the line-to-line voltage by the square root of three.

Phase-to-ground voltage = 13,200 V / 1.732 = approximately 7,621 V

Therefore, the nominal phase-to-ground voltage is approximately 7.62 kV RMS.

For a phase-to-ground connected surge arrester, the MCOV must be at least equal to the highest continuous power-frequency voltage expected across the arrester during normal operation.

Using nominal voltage alone is insufficient because actual system voltage may exceed its nominal value.

For example, if the maximum system line-to-line operating voltage is 13.97 kV, the corresponding balanced phase-to-ground voltage is:

13.97 kV / 1.732 = approximately 8.07 kV RMS

An arrester with an 8.4 kV MCOV would exceed this calculated continuous voltage. However, the suitability of that arrester still depends on grounding conditions, temporary overvoltages, and the applicable manufacturer's ratings.

Which Surge Arrester Ratings Are Commonly Considered for 13.2 kV Systems

The following table provides preliminary engineering guidance for phase-to-ground connected metal-oxide surge arresters on nominal 13.2 kV distribution systems.

System Configuration Preliminary Arrester Rating Typical MCOV Engineering Consideration
Four-wire grounded-wye, multigrounded neutral 10 kV 8.4 kV Common distribution application; verify maximum voltage and TOV
Three-wire system, solidly grounded at source 15 kV may be considered 12.7 kV Ground-fault voltage rise and clearing time govern selection
Ungrounded delta or ungrounded-wye 18 kV may be considered 15.3 kV Unfaulted phases may approach line-to-line voltage relative to ground
Resistance-grounded or impedance-grounded Application-specific Application-specific Requires evaluation of neutral displacement and TOV duration

Important: These values are preliminary selection examples, not universal specifications. Arrester ratings and corresponding MCOV values must be verified against the selected manufacturer's product data. Some ungrounded systems may permit lower ratings when documented fault-clearing times and TOV withstand curves support their use.

Why a 10 kV Surge Arrester May Be Suitable for a Grounded 13.2 kV Transformer

A 10 kV rated arrester with an 8.4 kV MCOV is commonly considered for a 13.2 kV grounded-wye, multigrounded-neutral distribution system because its continuous voltage capability exceeds the nominal 7.62 kV phase-to-ground voltage.

This configuration can provide effective transformer surge protection when the source grounding limits temporary overvoltages and the selected arrester provides adequate insulation coordination.

However, the 10 kV rating does not mean that the arrester begins conducting only when voltage reaches 10 kV. Metal-oxide surge arresters have nonlinear voltage-current characteristics and conduct increasing current as applied voltage rises.

The rated voltage and MCOV represent different operating characteristics:

  • Rated voltage: A designated RMS power-frequency voltage associated with the arrester's standardized operating-duty performance.
  • MCOV: The maximum RMS power-frequency voltage that can be applied continuously across the arrester under specified operating conditions.
  • Discharge voltage: The voltage developed across the arrester while conducting a specified surge current.

The arrester must withstand normal system voltage and anticipated temporary overvoltages while limiting transient surges to levels compatible with transformer insulation.

Why Ungrounded and Delta Systems May Require Higher Arrester Ratings

Ungrounded and delta-connected systems can experience substantial phase-to-ground voltage changes during single-line-to-ground faults.

Under normal balanced operation, the phase-to-ground voltages may be approximately equal to the line-to-line voltage divided by the square root of three. During a ground fault, however, the unfaulted phases can rise toward the full line-to-line voltage relative to ground.

For a nominal 13.2 kV system, this means an unfaulted phase may experience approximately 13.2 kV RMS to ground during certain fault conditions.

An arrester with an 8.4 kV MCOV cannot automatically be assumed suitable for this condition.

Similarly, a 15 kV rated arrester with a 12.7 kV MCOV should not automatically be considered adequate for an ungrounded 13.2 kV system. Its suitability depends on the maximum system voltage and the magnitude and duration of temporary overvoltages.

An 18 kV rated arrester with a typical 15.3 kV MCOV may be a more conservative preliminary candidate for some ungrounded applications, subject to manufacturer data and insulation coordination.

The engineer should also evaluate the possibility of intermittent arcing ground faults, resonance, and other operating conditions that can produce overvoltages beyond a simple steady-state calculation.

How Transformer Capacity Affects Surge Arrester Selection

The transformer capacity of 2.5 MVA does not directly establish the required surge arrester kV rating.

Surge arrester voltage ratings are selected primarily according to system voltage, grounding, and overvoltage conditions.

Transformer capacity remains relevant to the broader electrical design because it influences rated current, equipment configuration, available fault-current calculations, and installation requirements.

For a three-phase transformer rated 2,500 kVA at 13.2 kV, the nominal primary full-load current is:

I = 2,500,000 VA / (1.732 x 13,200 V)

I = approximately 109.3 amperes

This current is useful for transformer and primary equipment design but is not the surge arrester's discharge-current rating.

Surge arresters conduct transient currents associated with lightning and switching events. Their required discharge-current capability, energy handling, and durability depend on the surge environment and arrester application class.

How MCOV and Temporary Overvoltage Determine Arrester Suitability

Maximum continuous operating voltage and temporary overvoltage withstand capability are two critical criteria for surge arrester selection.

MCOV establishes the highest continuous RMS voltage that may be applied across the arrester. Temporary overvoltage capability describes the arrester's ability to survive higher power-frequency voltages for limited durations.

Temporary overvoltages may result from:

  • Single-line-to-ground faults
  • Neutral displacement or loss of grounding reference
  • Load rejection and abnormal operating conditions
  • Transformer energization and certain ferroresonance conditions
  • Other system disturbances that elevate power-frequency voltage

For engineering verification, the anticipated TOV magnitude and duration should be compared with the manufacturer's TOV withstand curve.

For example, a system that experiences a temporary phase-to-ground voltage of 12 kV for a short fault-clearing interval may permit an arrester with an MCOV below 12 kV if the manufacturer's TOV curve explicitly supports that magnitude and duration.

The same arrester may be unsuitable if the overvoltage persists for an extended period.

Surge arresters are designed to limit transient overvoltages. They are not intended to continuously regulate or eliminate sustained power-frequency overvoltages.

How Transformer BIL Influences Surge Arrester Selection

Basic insulation level, or BIL, identifies the standardized lightning impulse withstand capability of electrical equipment.

For medium-voltage transformers, BIL is an essential part of insulation coordination because the selected arrester must limit surge voltage sufficiently below the transformer's applicable impulse withstand level.

A transformer designed for a 15 kV voltage class may commonly have a 95 kV BIL, but this value must be verified from the actual transformer nameplate and manufacturer documentation.

The engineering evaluation should consider:

  • Transformer lightning impulse withstand rating
  • Arrester lightning impulse discharge voltage
  • Front-of-wave protective characteristics
  • Switching surge protective performance where applicable
  • Voltage contributions from arrester leads and grounding connections
  • Required insulation coordination margins

The effective voltage reaching the transformer terminals can exceed the arrester's published discharge voltage because of inductive voltage drops and traveling-wave effects associated with installation geometry.

Therefore, an arrester should generally be installed as close as practicable to the transformer terminals, with short, appropriately routed line and grounding connections.

Increasing the arrester's voltage rating can improve its ability to withstand system overvoltages, but it may also increase its discharge voltage. Consequently, selecting the highest available rating is not necessarily the best protection strategy.

Which IEEE Standards Apply to Medium-Voltage Transformer Surge Protection

Several IEEE standards provide the technical framework for surge arrester performance, transformer insulation coordination, and medium-voltage system design.

  • IEEE C62.11: Establishes performance and testing requirements for metal-oxide surge arresters used on AC power circuits above 1 kV.
  • IEEE C62.22: Provides application guidance for selecting and applying metal-oxide surge arresters, including MCOV, TOV, and insulation coordination considerations. Engineers should verify the applicable published edition and revision status.
  • IEEE C62.82.1: Provides guidance for insulation coordination, including relationships between equipment insulation withstand and protective devices.
  • IEEE C57.12.00: Establishes general requirements for liquid-immersed distribution, power, and regulating transformers.
  • IEEE C57.12.01: Establishes general requirements for dry-type distribution and power transformers.

Relevant requirements of the National Electrical Code (NEC), NFPA 70, should also be considered for U.S. installations.

NEC Article 280 addresses surge arresters installed on systems operating above 1,000 volts. Its requirements include provisions relating to selection, installation, and connections.

NEC Article 450 addresses transformer installations, including applicable protection and installation requirements.

NEC requirements do not replace the need for an engineering evaluation of arrester MCOV, temporary overvoltage withstand, or insulation coordination.

For Canadian installations, the applicable Canadian Electrical Code, CSA C22.1, provincial requirements, utility standards, and relevant CSA or IEC equipment standards should be reviewed.

Applicable code editions and requirements depend on the installation location and authority having jurisdiction.

Where Surge Arresters Should Be Installed on a 13.2 kV Transformer

For a three-phase medium-voltage transformer, surge arresters are commonly installed on the primary side, with one appropriately rated arrester connected from each phase to ground.

The installation should minimize the electrical distance between the arrester and the equipment being protected.

Typical installation considerations include:

  • Positioning arresters near the high-voltage bushings or incoming primary terminals
  • Minimizing phase-lead and ground-lead lengths
  • Providing effective grounding and bonding
  • Maintaining required electrical clearances
  • Selecting arresters suitable for indoor or outdoor environmental exposure
  • Coordinating arrester placement with incoming cable terminations and switching equipment

Where long cable runs, overhead-to-underground transitions, or multiple pieces of medium-voltage equipment are involved, additional surge protection locations may be necessary.

The appropriate arrangement should be determined through system-specific insulation coordination and surge exposure analysis.

Practical Example of Surge Arrester Selection for a 2.5 MVA Transformer

Consider a 2.5 MVA, three-phase industrial transformer connected to a nominal 13.2 kV grounded-wye distribution system.

Assume the following preliminary design conditions:

  • Transformer capacity: 2,500 kVA
  • Primary voltage: 13,200 V line-to-line
  • System frequency: 60 Hz
  • Grounding: Four-wire grounded-wye, multigrounded neutral
  • Maximum operating voltage: 13.97 kV line-to-line
  • Transformer BIL: Assumed 95 kV, subject to nameplate verification
  • Arrester connection: Phase-to-ground at the transformer primary

Step 1: Calculate the Maximum Phase-to-Ground Voltage

13,970 V / 1.732 = approximately 8,066 V RMS.

The calculated maximum continuous phase-to-ground voltage is approximately 8.07 kV.

Step 2: Identify a Preliminary MCOV

A common 10 kV rated metal-oxide arrester has an MCOV of 8.4 kV.

Because 8.4 kV exceeds the calculated maximum continuous phase-to-ground voltage of 8.07 kV, it satisfies this initial voltage comparison.

Step 3: Verify Temporary Overvoltage Capability

The engineer must determine the maximum anticipated temporary phase-to-ground overvoltage and fault-clearing duration.

These conditions must fall within the selected manufacturer's TOV withstand characteristics.

Step 4: Verify Insulation Coordination

The arrester's published protective characteristics must be compared with the transformer's verified BIL and other applicable insulation withstand ratings.

Lead length, installation geometry, and required protective margins must be included in the evaluation.

Step 5: Confirm the Final Equipment Specification

If the MCOV, TOV, protective margins, energy handling, and installation requirements are satisfied, a 10 kV rated arrester with an 8.4 kV MCOV may be an appropriate selection.

If the actual system grounding, maximum operating voltage, or temporary overvoltage conditions differ from these assumptions, a different arrester rating may be necessary.

Common Surge Arrester Selection Mistakes to Avoid

Incorrect arrester selection can result in inadequate transformer protection or premature arrester failure.

Common engineering mistakes include:

  • Selecting by transformer MVA alone: Transformer capacity does not determine the required arrester voltage rating.
  • Using nominal line-to-line voltage as the arrester MCOV: The voltage across the arrester depends on its connection and system grounding.
  • Ignoring maximum system voltage: Actual operating voltage may exceed nominal voltage.
  • Assuming all grounded systems behave identically: Multigrounded distribution systems and three-wire grounded systems may have different temporary overvoltage characteristics.
  • Using a 15 kV arrester automatically on every 13.2 kV system: The voltage class of the transformer does not establish the correct arrester rating.
  • Ignoring temporary overvoltage duration: Ground-fault clearing time can determine whether a particular MCOV is acceptable.
  • Ignoring transformer BIL: An arrester that survives the electrical environment may still provide insufficient protective margin.
  • Using unnecessarily long arrester leads: Lead inductance can increase the voltage appearing at protected transformer terminals.

Frequently Asked Questions About 13.2 kV Transformer Surge Arresters

What size surge arrester is commonly used for a 13.2 kV transformer

A 10 kV rated surge arrester with an 8.4 kV MCOV is a common preliminary selection for a 13.2 kV grounded-wye, multigrounded-neutral distribution system. Other grounding configurations may require higher ratings. Final selection depends on maximum system voltage, temporary overvoltage capability, and insulation coordination.

Can a 15 kV surge arrester be used on a 13.2 kV system

Yes. A 15 kV rated arrester with a typical 12.7 kV MCOV may be appropriate for certain 13.2 kV systems. However, it is not automatically the preferred rating. The engineer must verify temporary overvoltage withstand and confirm that the arrester provides adequate protective margins for the transformer.

Does a 2.5 MVA transformer require a larger surge arrester than a 1 MVA transformer

Not necessarily. Transformers of different capacities operating on the same electrical system may use the same surge arrester voltage rating. Arrester class, discharge capability, energy handling, and installation requirements must still be evaluated for each application.

What is the difference between surge arrester rated voltage and MCOV

Rated voltage is a standardized arrester designation associated with operating-duty performance. MCOV is the maximum RMS power-frequency voltage that the arrester can withstand continuously under specified conditions. Both values are important, but MCOV is especially important when comparing an arrester with normal system operating voltage.

Why does transformer grounding affect surge arrester selection

Grounding determines how phase-to-ground voltages behave during normal operation and ground faults. Ungrounded or impedance-grounded systems may experience greater voltage rise on unfaulted phases than effectively grounded systems, requiring different arrester MCOV or TOV capabilities.

How many surge arresters are typically required for a three-phase transformer

Three surge arresters are commonly used for phase-to-ground protection on a three-phase transformer primary, with one arrester connected to each phase. Additional arresters or alternative arrangements may be necessary depending on system configuration and insulation coordination requirements.

Final Engineering Recommendations for 13.2 kV Transformer Surge Protection

For a 2.5 MVA transformer operating at 13.2 kV, the correct surge arrester rating cannot be determined from transformer capacity and nominal voltage alone.

A 10 kV rated arrester with an 8.4 kV MCOV is a reasonable preliminary candidate for a grounded-wye, multigrounded-neutral distribution system when the maximum continuous phase-to-ground voltage and temporary overvoltage requirements are satisfied.

Three-wire grounded, resistance-grounded, and ungrounded systems may require higher ratings or a more detailed engineering evaluation.

Final selection should follow applicable IEEE guidance and manufacturer specifications, with documented verification of MCOV, TOV, insulation coordination, surge performance, and installation conditions.

For additional information about transformer configurations, voltage classes, and industrial power applications, explore Larson Electronics' industrial transformers.

For assistance evaluating transformer requirements and medium-voltage electrical equipment for industrial applications, contact Larson Electronics.